Analysis of vapor compression refrigeration cycle using advanced exergetic approach with Taguchi and ANOVA optimization and refrigerant selection with enviroeconomic concerns by TOPSIS analysis

dc.contributor.authorUstaoğlu, Abid
dc.contributor.authorKurşuncu, Bilal
dc.contributor.authorKaya, Alaattin Metin
dc.contributor.authorCaliskan, Hakan
dc.contributor.authorKurşuncu, Bilal
dc.contributor.authorUstaoğlu, Abid
dc.date.accessioned2025-10-18T09:58:25Z
dc.date.created2022
dc.date.issued2022
dc.departmentFakülteler, Mühendislik Mimarlık ve Tasarım Fakültesi, Makine Mühendisliği Bölümü
dc.description.abstractIn this study, TOPSIS analysis was applied to decide the optimum refrigerants with cost, safety, environmental and enviroeconomic concerns along with thermophysical properties. A vapor compression refrigeration cycle performance was investigated with the statistical and thermodynamic approaches. COP, exergy efficiency, total, avoidable, and unavoidable exergy destruction rates were calculated for various experimental designs. According to the relative proximity to the ideal solution, the best refrigerants for the system were determined as R513a, R134a, and R448a, respectively. The optimum parameters for the greatest COP and exergetic performance were calculated as A(2)B(3)C(1)D(3)E(3)F(1). In the optimum case, the best COP and exergy efficiency of 2.65 and 10% and the lowest total exergy destruction of 0.34 kW were achieved for R134a. These are larger than all other 27 experimental patterns. The parameters having an impact on the COP, exergy efficiency, and total exergy destruction rate were found as T-EVA > T-CON > Refrigerant > eta(COM,H) > eta(COM,L) > P-in (B > C > A > E > D > F). The evaporator temperature is the most effective parameter on the performance with about 42.8% for the performance. It is followed by that of condenser and refrigerant to be 32.5% and 13.8%. The most effective parameters for the avoidable exergy destruction rate were high-and low-pressure compressors efficiencies, evaporator temperature, and condenser temperature, respectively.
dc.identifier.doi10.1016/j.seta.2022.102182
dc.identifier.issn2213-1388
dc.identifier.issn2213-1396
dc.identifier.orcidUSTAOGLU, Abid/0000-0003-3391-5015
dc.identifier.orcidKaya, Alaattin/0000-0002-1940-8749;
dc.identifier.scopus2-s2.0-85126959815
dc.identifier.scopusqualityQ1
dc.identifier.urihttps://doi.org/10.1016/j.seta.2022.102182
dc.identifier.urihttps://hdl.handle.net/11772/19676
dc.identifier.volume52
dc.identifier.wosWOS:000804664000001
dc.identifier.wosqualityQ1
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherElsevier
dc.relation.ispartofSustainable Energy Technologies and Assessments
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.snmzWoS_20251016
dc.subjectVapor-Compression Multistage Refrigeration
dc.subjectAdvanced Exergy Analysis
dc.subjectRefrigerant Selection
dc.subjectTaguchi
dc.subjectAnova
dc.subjectTopsis
dc.titleAnalysis of vapor compression refrigeration cycle using advanced exergetic approach with Taguchi and ANOVA optimization and refrigerant selection with enviroeconomic concerns by TOPSIS analysis