dc.identifier.citation | Parıltı, M. B. (2019). Güneş enerjisi kaynaklı absorpsiyonlu bir soğutma sisteminin ileri ekserji analizi. Yayımlanmamış yüksek lisans tezi. Bartın: Bartın Üniversitesi Fen Bilimleri Enstitüsü | en_US |
dc.identifier.uri | http://hdl.handle.net/11772/2233 | |
dc.description | 06.03.2018 tarih ve 30352 sayılı Resmi gazetede yayımlanan “Yükseköğretim Kanunu İle Bazı Kanun Ve Kanun Hükmünde Kararnamelerde Değişiklik Yapılması Hakkında Kanun” ile 18.06.2018 tarihli “Lisansüstü Tezlerin Elektronik Ortamda Toplanması, Düzenlenmesi ve Erişime Açılmasına İlişkin Yönerge” gereğince tam metin erişime açılmıştır. | en_US |
dc.description.abstract | Bu çalışmada, güneş enerjisi kaynaklı absorpsiyonlu bir soğutma sisteminin ileri ekserji analizi gerçekleştirilmiştir. Bu çalışmanın amacı sistem parametrelerinin sistem performansı üzerindeki etkisini incelemektir. Öncelikle farklı literatür çalışmaları incelenmiş ve uygulamada var olan sistemler hakkında araştırmalar yapılmıştır. Ayrıca çalışmada absorpsiyonlu çalışma sistemlerinin türleri ve çalışma sıvılarının çeşitliliğinden bahsedilmiştir. EES programında tek etkili absorpsiyonlu soğutma sistemlerinin analizini yapmak için amonyak-su akışkan çifti seçilmiştir. Amonyak soğutucu akışkan olarak seçilirken absorbent olarak amonyak-su eriyiği seçilmiştir. Termodinamiğin birinci yasası kullanılarak her bir komponent için kütle ve enerji denge eşitlikleri oluşturulmuştur. Böylece çevrimdeki her bir noktanın entalpi ve entropi değerleri hesaplanmıştır. Sistemin enerji analizi yapıldıktan sonra termodinamiğin ikinci yasasını kullanarak sistemde bulunan komponentlerin geleneksel ekserji değerleri hesaplanmıştır. Sistemin soğutma performansı (COP), ekserji verimi ve her bir komponentin ekserji yıkımları bulunmuştur. Geleneksel ekserji analizi daha detaylı analiz sonuçları elde etmede yetersiz kalmaktadır. Bu yüzden daha hassas sonuçlar elde etmek için ileri ekserji analizine ihtiyaç duyulmaktır. İleri ekserji analizi sayesinde sistemde bulunan komponentler arasındaki ilişkiyi ve geliştirme potansiyelleri belirlenmiştir. Sistemin toplam ekserji yıkımı 16.45 kW, soğutma performansı 0.3 ve ekserji verimi %30 olarak hesaplanmıştır. Genleşme valfi1 ve pompa en küçük kaçınılabilir ekserji yıkım oranına sahip komponentlerdir. | en_US |
dc.description.abstract | In this study, advanced exergy analysis of an absorption cooling system based on solar energy was performed. The aim of this study is to investigate the effect of system parameters on system performance. Firstly, different literature studies have been evaluated and researches have been made about the existing systems in practice. In addition, the types of working systems with absorption and the variety of working fluids were mentioned. In the EES program, the ammonia-water fluid pair was selected to analyze single-effect absorption cooling systems. Ammonia was chosen as refrigerant and ammonia-water solution was chosen as absorbent. Using the first law of thermodynamics, the mass and energy balance equations for each component were found. Thus, enthalpy and entropy values of each point in the cycle and thermodynamic properties of fluids were calculated. After the energy analysis of the system, conventional exergy values of the components in the system were calculated by using the second law of thermodynamics. The cooling performance (COP) of the system was found. Conventional exergy analysis fails to obtain more detailed analysis results. Therefore, further exergy analysis is needed to obtain more accurate results. Further exergy analysis identified the relationship between the components in the system and their development potential. Total exergy destruction of the system was calculated as 16.45 kw, cooling performance was 0.3 and exergy efficiency was calculated as 30%. The expansion valve1 and pump are the components with the smallest avoidable exergy destruction rate. | en_US |
dc.language.iso | tur | en_US |
dc.publisher | Bartın Üniversitesi, Fen Bilimleri Enstitüsü | en_US |
dc.rights | info:eu-repo/semantics/openAccess | en_US |
dc.subject | Absorpsiyonlu soğutma sistemi | en_US |
dc.subject | Tek etkili | en_US |
dc.subject | Amonyak-Su | en_US |
dc.subject | Enerji analizi | en_US |
dc.subject | Ekserji analizi | en_US |
dc.subject | Çevirim | en_US |
dc.subject | Akışkan çifti | en_US |
dc.subject | Absorption refrigeration system | en_US |
dc.subject | Single effect | en_US |
dc.subject | Ammonia-Water | en_US |
dc.subject | Energy analysis | en_US |
dc.subject | Exergy analysis | en_US |
dc.subject | Cycle | en_US |
dc.subject | Fluid pair | en_US |
dc.title | Güneş enerjisi kaynaklı absorpsiyonlu bir soğutma sisteminin ileri ekserji analizi | en_US |
dc.title.alternative | Advanced exergy analysis of a solar energy powered absorption refrigeration system | en_US |
dc.type | masterThesis | en_US |
dc.contributor.department | Bartın Üniversitesi, Fen Bilimleri Enstitüsü, Makine Mühendisliği Ana Bilim Dalı | en_US |